6.6.2 Derating for Altitude
The cooling capability of air is decreased at lower air pressure. No derating is necessary at or below 1000 m (3281 ft). Above
1000 m (3281 ft), the ambient temperature (T
Illustration 6.2.
6
6
Illustration 6.2 Derating of Output Current Based on Altitude at T
Illustration 6.2 shows that at 41.7 °C (107 °F), 100% of the rated output current is available. At 45 °C (113 °F) (T
K), 91% of the rated output current is available.