Danfoss VLT AutomationDrive FC 361 Series Design Manual page 54

90–315 kw, enclosure sizes j8–j9
Hide thumbs Also See for VLT AutomationDrive FC 361 Series:
Table of Contents

Advertisement

Electrical Installation Con...
7.13.1 EMC Test Results
The following test results have been obtained using a drive (with options if relevant), a shielded control cable, a control box
with potentiometer, a motor, and motor shielded cable.
RFI filter type
Standards and
requirements
FC 361
7
7
Table 7.14 EMC Test Results (Emission and Immunity)
7.13.2 Emission Requirements
According to the EMC product standard for adjustable speed drives EN/IEC 61800-3:2004, the EMC requirements depend on
the environment in which the drive is installed. These environments along with the mains voltage supply requirements are
defined in Table 7.15.
The drives comply with EMC requirements described in IEC/EN 61800-3 (2004)+AM1 (2011), category C3, for equipment
having greater than 100 A per-phase current draw, installed in the 2
150 m (492 ft) shielded motor cable.
Category
(EN 61800-3)
C1
C2
C3
C4
Table 7.15 Emission Requirements
When the generic emission standards are used, the drives are required to comply with Table 7.16.
Environment
First environment
(home and office)
Second environment
(industrial environment)
Table 7.16 Generic Emission Standard Limits
52
EN 55011
Class B
Housing,
trades, and
light
industries
EN/IEC 61800-3
Category C1
First
environment
Home and
office
90–315 kW
No
380–480 V
Definition
First environment (home and office) with a supply voltage less than 1000 V.
First environment (home and office) with a supply voltage less than 1000 V, which
is not plug-in or movable and where a professional is intended to be used to
install or commission the system.
Second environment (industrial) with a supply voltage lower than 1000 V.
Second environment with the following:
Supply voltage equal to or above 1000 V.
Rated current equal to or above 400 A.
Intended for use in complex systems.
Generic standard
EN/IEC 61000-6-3 Emission standard for residential, commercial,
and light industrial environments.
EN/IEC 61000-6-4 Emission standard for industrial environments.
Danfoss A/S © 03/2019 All rights reserved.
VLT® AutomationDrive FC 361
Conducted emission
Class A
Class A
group 1
group 2
Industrial
Industrial
environment
environment
Category C2
Category C3
First
Second
environment
environment
Home and
Industrial
office
No
150 m
(492 ft)
nd
environment. Compliance testing is performed with a
Radiated emission
Class B
Class A
Housing, trades,
group 1
and light
Industrial
industries
environment
Category C1
Category C2
First
First environment
environment
Home and office
Home and office
No
No
Conducted emission
(EN 55011)
Class B
Class A Group 1
Class A Group 2
No limit line.
An EMC plan must be made.
Conducted emission requirement
according to EN 55011 limits
Class B
Class A Group 1
Class A
group 2
Industrial
environment
Category C3
First
environment
Home and
office
Yes
MG06K102

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AutomationDrive FC 361 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents