Electrical Installation Con...
NOTICE
PELV COMPLIANCE
Prevent electric shock by using protective extra low
voltage (PELV) electrical supply and complying with local
and national PELV regulations.
7
7
1
2
3
4
L1
L2
L3
PE
5
1
PLC
2
Minimum 16 mm
3
Control cables
4
Minimum 200 mm (7.9 in) between control cables, motor
cables, and mains cables
5
Mains supply
6
Bare (unpainted) surface
7
Star washers
8
Brake cable (shielded)
9
Motor cable (shielded)
Illustration 7.18 Example of Proper EMC Installation
56
VLT® AutomationDrive FC 361
2
(6 AWG) equalizing cable
Danfoss A/S © 03/2019 All rights reserved.
90
4
4
PE
10
Mains cable (unshielded)
11
Output contactor
12
Cable insulation stripped
13
Common ground busbar. Follow local and national
requirements for cabinet grounding
14
Brake resistor
15
Metal box
16
Connection to motor
17
Motor
18
EMC cable gland
6
7
8
9
10
11
12
13
14
15
u
16
v
w
17
18
MG06K102