Table 15: Control Byte C0; Table 16: Status Byte S0; Table 17: Control Byte C1 - WAGO 750 Series Manual

Serial interface rs-232 / rs-485
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-652 Serial Interface RS-232 / RS-485

Table 15: Control byte C0

Bit 7
RC
TR
RA
IR
SC
OL 0
OL1
OL2
RC

Table 16: Status byte S0

Bit 7
RC
TA
RR
IA
IL0
IL1
IL2
BUF_F
RC

Table 17: Control byte C1

Bit 7
0
OL3
OL4
OL5
0
Manual
1.2.0
Bit 6
Bit 5
OL2
OL1
Transmit request
Receive acknowledge
Initialization request
Send continuous (of data from the FIFO)
Output length (number of characters to be sent that were stored in the output
data, bit 0)
Output length (number of characters to be sent that were stored in the output
data, bit 1)
Output length (number of characters to be sent that were stored in the output
data, bit 2)
Reserved for internal communication
Bit 6
Bit 5
BUF_F
IL2
Transmit acknowledge
Receive request
Initialization acknowledge
Input length (number of characters received that are available in the input data,
bit 0)
Input length (number of characters received that are available in the input data,
bit 1)
Input length (number of characters received that are available in the input data,
bit 2)
Buffer full (message: input buffer is full)
Reserved for internal communication
Bit 6
Bit 5
0
Output length (number of characters to be sent that were stored in the output
data, bit 3)
Output length (number of characters to be sent that were stored in the output
data, bit 4)
Output length (number of characters to be sent that were stored in the output
data, bit 5)
This constant must be set to 0.
Bit 4
Bit 3
OL0
SC
Bit 4
Bit 3
IL1
IL0
Bit 4
Bit 3
0
Process Image
Bit 2
Bit 1
IR
RA
Bit 2
Bit 1
IA
RR
Bit 2
Bit 1
OL5
OL4
29
Bit 0
TR
Bit 0
TA
Bit 0
OL3

Hide quick links: