6.2 First Time Switch On

Before switching power on, ensure that the system has been commissioned or that a qualified person has checked
that the wiring is safe and conforms to local regulations, and that all electrical connections are made in accordance
with Chapter 5
Switch on power at the Isolator switch and wait for the system to initialise.
The system start up sequence may last for up to 20 minutes depending on the number of channels in use. During this
time the mA Output signals and Relay Output contacts are initialised to the inhibit state, with the Relay output being
delayed by approximately 30 seconds after the mA output inhibit ends.
Each sensor requires the warm-up time for stabilization. When Touchpoint Plus is turned-on, Touchpoint Plus starts
the normal gas reading after sensor warm-up period. Refer to each sensor's user manual for the warm-up time.
TPPL will first display the auto-scrolling Input screen, indicating the current status of the system. The Channel List
View is shown below. The screenshot shows installed sensors but it may be blank depending on your system status:
You can alter the screen views or gain further information by touching the icons shown below:
Toggle to select screen layout
SD Card Status Good
SD Card Status Fault
External mains power is connected.
Touch for status
External power is not connected.
Touch for status
Event History (changes colour to
show fault, inhibit or alarm)
Further Menu Options
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Table 12.

Home Screen Menu Icons

53
Admin Logged in
Service Logged in
Operator Logged in
No one Logged in
Toggle auto-scroll on and off
Scroll up when auto-scroll disabled
Scroll down when auto-scroll disabled
Commissioning
Touchpoint Plus
Technical Handbook