7 Commissioning and Configuration
7.1 First Time Switch On
7.1.1 Pre-power Check
1. Check that the working environment temperature is within the range given in the Specifications section of this manual.
2. Check that the Searchzone Sonik detector is mounted correctly and secured in its position. Refer to the Mechanical Installation and
Electrical Installation sections of this manual for more information.
3. Check that the Searchzone Sonik unit is wired correctly. Refer to the Electrical Installation section of this manual for more
information.
7.2 Operating Function Verification
Check that the Searchzone Sonik detector safety outputs are working properly.
Check that the Searchzone Sonik detector is positioned correctly so as to cover the risk being monitored.
Perform a functional test where appropriate.
7.3 Communication
NOTE
The prerequisite to commissioning using Bluetooth is to have the Searchzone Sonik Mobile App installed to a suitably-approved mobile
device and that the user be fully registered to the Honeywell User Management Server (UMS).
7.3.1 Bluetooth®
The Searchzone Sonik detector features a Bluetooth interface that allows non-intrusive connection using a mobile device running the
Searchzone Sonik App. The Bluetooth interface is accessed by the mobile device that supports Bluetooth.
Refer to the Mobile App section of this manual for more information on Bluetooth communication link.
The Searchzone Sonik detector supports Bluetooth point-to-point mode of operation. While there is a connection between the
Searchzone Sonik and a mobile device, the detector cannot be scanned or accessed by another mobile device.
If there is no active Bluetooth communication for 10 minutes, the Searchzone Sonik detector will terminate the Bluetooth connection
automatically.
The communication range will vary depending on the field situation and installation location of Searchzone Sonik. Optimal range will be
achieved when line-of-sight between the Searchzone Sonik detector and the mobile device is achieved.
7.4 Settings and Configuration
The Searchzone Sonik Mobile App is the primary tool for configuring the detector. The configurable settings are as follows:
Detector ID
Operation mode
Algorithm mode
Inhibit level
Alarm set point
Warning level
Refer to the Mobile App section of this manual for more instructions and guidance on installation, commissioning and maintenance.
NOTE
When used with a Touchpoint Pro controller, the positive and negative suppression values must be set correctly otherwise the controller
will report a detector fault. Similarly, when used with a Touchpoint Plus controller, the upper and lower deadband values must be set up.
PN 2331M1220 Issue 1
Fault level
Over-range level
Alarm 1 level
Alarm 2 level
Alarm delay
Proof test interval
Searchzone Sonik − Technical Manual
7 Commissioning / First Time Operation / Configuration
Relay 1, Relay 2, Relay 3
LED mode
LED intensity
Inhibit timeout period
Set access PIN
37