Routine Testing; Exercising The Audio/Visual Alarms - Honeywell Touchpoint Plus Technical Handbook

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

8.2 Routine Testing

8.2.1 Exercising the Audio/Visual Alarms

Audio/visual alarms can be tested by switching the Dedicated Alarms On. To do this:
1) Ensure that relay activated output systems (i.e. emergency deluge / sirens etc.) are isolated before starting the
test.
2) Login as an Administrator or Service.
3) Touch
Menu>System Test >Dedicated Alarm Contacts
4) Touch the appropriate Alarm to toggle it on for each output (see below).
5) Check the alarm outputs are visible / audible and turn them off when satisfied.
6) Touch [Finish] when the tests are completed and all selections will automatically turn off.
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Routine Maintenance and Scheduled Testing
Ensure that the system is returned to normal operation once testing is complete.
.
CAUTION
105
Touchpoint Plus
Technical Handbook