Ma Input Module Connections - Honeywell Touchpoint Plus Technical Handbook

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

5.2.10 mA Input Module Connections

Note: mA input channels are limited to 20 W per channel to a combined total of 40 W (68 W if Main Module Terminals
13 to 21 are not used). Sensors requiring more than 20 W must have their own power supplies.
Module Label
mA Input 1
mA Input 2
mA Input 3
mA Input 4
mA Input 5
mA Input 6
mA Input 7
mA Input 8
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Electrical Power Connection and Interfacing
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Table 6.

mA Input Module Connections

Three Wire Device Powered by a mA Input Module
39
Identifier
Field device
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
+VE
+24 VDC
VE
0 VDC
Sig
4 20 mA signal
Touchpoint Plus