Honeywell Touchpoint Plus Technical Handbook page 148

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

Event
Code
Type
Fault
6
Supplied voltage fault
Fault
7
Internal software failure
Fault
8
Modbus communication failure
Fault
9
Sensor fault (including signal range fault)
Fault
10
Analogue output mismatched
Fault
11
Relay not controlled
Remote fault informed by detector
Fault
12
(depending on fault signal range)
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Long Description
148
Display in Event
Triggered
History
IO board /
Supplied voltage fault
Main board
[B/D Type], Code: xxx
Internal software
IO board /
fault
Main board
[B/D Type], Code: xxx
Modbus Comm Fault
IO board
CH: xx, Node: xx
Sensor Fault
IO board
CH: xx, [B/D Type],
Code: xx
mA Output Error
IO board
CH: xx
IO board /
Relay Output Error
Main board
CH: xx
Detector In Fault
IO board
CH: xx, [B/D Type]
Event Codes
Details
B/D type
0:Main, 1:UI, 2:mA
Input, 3 : mV input,
4:Relay, 5:mA output,
7:Modbus,
7:Extension power
Code
0: Vapp low, 1: V5
low, 2: V3.3 low, 3:
V12 low, 4: V9 low
B/D type
0:Main, 1:UI, 2:mA
Input, 3 : mV input,
4:Relay, 5:mA output,
7:Modbus,
7:Extension power
Code
0: BUFFER
OVERFLOW,
1: instruction test
failed
2: Sequence Checking
failed
B/D type
0:Main, 1:UI, 2:mA
Input, 3 : mV input,
4:Relay, 5:mA output,
7:Modbus,
7:Extension power
Code
0 : bead open/short
1 : line open/short
2 : detector short
3 : operating voltage
fault
4: driver current fault
B/D type
0:Main, 1:UI, 2:mA
Input, 3 : mV input,
4:Relay, 5:mA output,
7:Modbus,
7:Extension power
Touchpoint Plus
Technical Handbook

Advertisement

Table of Contents
loading

Table of Contents