6.8 Remote Reset / Acknowledge / Inhibit Switch Options

Select this option if your system has been installed with Remote switches that supplement the local Alarm
Acknowledge, Alarm Reset, or Channel Inhibit options.
1) Confirm whether the remote inhibit switches are normally open circuit or normally closed. (Single stand-alone
switches can be either mode but multiple switches must be normal closed circuit if wired in series and normal
open circuit if wired in parallel.)
2) Login as Service or Administrator.
3) Touch
Menu>Configuration>Security>Remote Access
4) Touch the required [Enable / Disable] options and whether the Remote Inhibit Setting is Normal Open or Normal
Closed.
5) Touch
Finish>Close>Close>User Icon>Log Out

6.9 Data Logging

You should set the Data Logging Interval and Threshold during initial configuration.
Using a 0 %FSD Threshold means that the TPPL will log the gas concentration at the specified intervals without
checking changes in gas concentration. In contrast, a >1 %FSD Threshold setting will ignore fluctuations in low
ambient gas concentrations and only check for rises in gas above the Threshold (i.e. safe) setting.
However, if you do want to monitor changes, you should start with a low threshold setting and slowly increase it by
trial and error it if you get too many unnecessary warnings.

6.9.1 To set or change Data Logging:

1) Log in as Administrator or Service.
2) Touch
Menu>Configuration>Log Interval & Threshold
3) Touch required box and enter the details using the touchpad.
4) Touch [Finish].
5) Make other changes or [Log Out].