Ma Output Module; Relay Output Module; Expansion Module; Power Supplies - Honeywell Touchpoint Plus Technical Handbook

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

11.3.4 mA Output Module

Description
Module Power Consumption (Max.)
Sensor Configuration
Signal Measurement Range
Loop Resistance

11.3.5 Relay Output Module

Description
Power Consumption Maximum
Relay Contacts
Relay Operation

11.3.6 Expansion Module

Cable between Basic and Expansion
units

11.4 Power Supplies

11.4.1 External Supplies

SMPS Power Supply
AC Input Voltage Range (~)
DC Input Voltage Range ( )
Input Frequency Range (~)
Output Voltage ( )
Dimension
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
4-channel Analogue Output Module for 2 wire 4 20 mA
signals
4.2 W (with 700 mA loop resistance @ 20 mA output)
2-wire current source, Isolated current loop output
0 20 mA (4 20 mA = 0 100% scale)
33 700 Ω
12-channel Relay Output Module incorporating 12 single
pole change over (SPDT) relays
2.5 W (with all relays energised)
1.7 A @ 250 VAC / 1.7 A @ 30 VDC
Individually configurable for normally energised / de-
energised operation
<10 m, 18 20 AWG, shielded twisted pair
156 W
AC 110/220 V ±10 % of nominal (manual switching)
DC 18 32 V SELV Supply
AC 50 60 Hz ± 6 %
DC 24 V
199 x 98 x 38mm (L x W x H)
125
Technical Specifications
Touchpoint Plus
Technical Handbook

Advertisement

Table of Contents
loading

Table of Contents