2.1.2 Safety Hazards

The following specific hazards are associated with the installation and use of this equipment:
Touchpoint Plus is Not ATEX/IECEx certified, and it shall only be installed in safe areas where there are no
flammable atmospheres, and where oxygen concentrations cannot exceed 25% v/v O
Touchpoint Plus is suitable for use in Class I, Division 2, Groups A, B, C, and D or non-hazardous locations
Lithium batteries may cause severe injury or death if swallowed, and may catch fire or explode if mishandled,
Always handle batteries with care, keep them out of the reach of children, and dispose of them carefully in
Batteries (regardless of type) shall only be handled, fitted, removed or replaced in non-hazardous (safe)
All power supplies must be hard wired and must include a circuit breaker (RCD / RCCB) and, close by and
unobstructed, a means of manually isolating and locking out the power supply without breaking the
Lethal current may be present in this equipment when electrical power is applied and after it is removed.
Isolate power before opening electrical access panels. Ensure residual current is fully discharged before
Lethal current may be generated both internally and externally to the system. All installations, including
enclosures and external units, must be grounded to protective earth, and must be capable of staying earthed
The Protective Earth (Ground) symbol is shown to the left, and it always has a green background. Do not
The Touchpoint Plus system and/or its sensors may become contaminated by the ambient environment in
which it or they are used. It is the
precautions are taken before handling any components or transferring them to any other party.
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
DANGER
WARNING
recharged, burned or disposed of incorrectly.
accordance with local regulations.
WARNING
protective earth (ground) connection.
Removable plug/socket connection is not permitted under any circumstance.
WARNING
There is a risk of death or injury from electrical shock when access doors are open.
WARNING
(grounded) when the power supply is interrupted.
confuse it with the chassis earth and equipment earth symbols shown below it.
WARNING
TOXIC WASTE AND HARMFUL BY-PRODUCTS
IGNITION HAZARD
only.
LITHIUM BATTERY HAZARDS
areas.
LETHAL VOLTAGE PRESENT
LETHAL VOLTAGE PRESENT
touching live terminals.
LETHAL VOLTAGE PRESENT
responsibility to ensure that all appropriate safety