6.16.2 How to Restore the Configuration

To restore a configuration, you must first copy the stored file
directory of an empty SD card (FAT32), and then an Administrator must follow the reverse process of backing up, i.e.
use [Import] instead of [Export].
Note:
\\CFG\TPP_CFG.bin
Note: Before attempting to restore from a saved configuration you must ensure that the current status is exactly the
same as it was when the backup file was exported. In other words the module installation status and commissioning
status must be exactly the same or the system will not import the configuration data.
Restoring the configuration does not include the gas calibration data. It could be necessary for user
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
must be inside the specific folder on the SD card.
to conduct the gas calibration after restoring the configuration.
[Your PC] \\CFG\TPP_CFG.bin