Honeywell Touchpoint Plus Technical Handbook page 137

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

Parameter Name
Target Resolution
Resolution
Inhibit Time-out
Inhibit Time-out
Alarm will be continued until manual user
Alarm Latch
reset if latching is enabled.
Calibration Interval
0, 30 to 365
Target Full Range
Min full range, Max full range and user
Alarm hysteresis is to avoid the alarm from
Threshold Alarm
frequent on/off when the gas reading is
Hysteresis
close to the alarm threshold.
Alarm 1 Enable
Alarm 1 enable/disable
Alarm 1 Threshold
Alarm 1 trigger option (Rising or Falling)
Trigger
Alarm 1 Level
Alarm 1 threshold concentration
Alarm 2 Enable
Alarm 2 enable/disable
Alarm 2 Threshold
Alarm 2 trigger option (Rising or Falling)
Trigger
Alarm 2 Level
Alarm 2 threshold concentration
Alarm 3 Enable
Alarm 3 enable/disable
Alarm 3 Threshold
Alarm 3 threshold concentration
Trigger
Alarm 3 Level
Alarm 3 threshold concentration
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Parameter
Description
Configurable Parameter Reference Guide
Applies
Read/
Range
to
Write
mA Input
R
0.001~100
mA Input
R/W
0~60
mA Input
R/W
Disable/Enable
mA Input
R/W
0, 30 to 365
mA Input
R/W
0~100000
mA Input
R/W
0~10
mA Input
R/W
Disable/Enable
mA Input
R/W
Rising/Falling
2%FSD ~
mA Input
R/W
100%FSD
mA Input
R/W
Disable/Enable
mA Input
R/W
Rising/Falling
2%FSD ~
mA Input
R/W
100%FSD
mA Input
R/W
Disable/Enable
mA Input
R/W
Rising/Falling
2%FSD ~
mA Input
R/W
100%FSD
137
Default Value
Remark
0.001, 0.002, 0.005, 0.01,
0.1
0.02, 0.05, 0.1, 0.2, 0.5, 1,
2, 5, 10, 20, 50, 100
10
0: Disable , minute
Enable
per channel
180
0 : Disable
Write available when:
Detector Name- User
Max full range
Detector. Max range in
catalogue file
2% of Full range
Disable
Rising
20% of Full range
Disable
Rising
0 Rising, 1 Falling
40% of Full range
Disable
Rising
60% of Full range
Technical Handbook
Touchpoint Plus