How To Replace A Faulty I/O Module; To Replace A Faulty Module - Honeywell Touchpoint Plus Technical Handbook

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

9.2 How to Replace a Faulty I/O Module

A faulty I/O module can be replaced with another of the same type, without needing to reprogram the configuration.
Touchpoint Plus will automatically copy over the configuration to the new module.
If the relays are switching mains voltages, hazardous live terminals may be present within the Relay Output
Module even if the Touchpoint Plus system is isolated. Isolate hazardous voltages before proceeding.
Note: The new module must be the same type and same or higher mod state as the module to be removed.

9.2.1 To Replace a Faulty Module

1) Login as an Administrator or Service.
2) Touch
Menu>Maintenance>Power off>Yes
3) Isolate the power supplies and then open the enclosure access door
4) Switch the battery to
5) Disconnect the faulty module.
6) Replace the module.
7) Reconnect the module.
8) Switch the battery to
9) Close and secure the enclosure door.
10) Switch on the Touchpoint Plus and wait for the system to stabilise.
11) Login as an Administrator or Service.
12) Touch
Menu>Configuration>Module Control Panel
13) In the Module Control panel, first touch [Refresh] and wait for the update to complete.
14) Touch the light blue block corresponding to the replaced module and touch
15) Wait until the update is completed and Log out when completed.
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
ANTI STATIC PRECAUTIONS
Antistatic Precautions are required to prevent damage to electronic components
(if there is a back-up battery installed).
(if there is a back-up battery installed).
Repairs, Replacements and Upgrades
WARNING
.
.
Key to I/O Module colour
Gray: Mandatory modules that cannot be added
removed or replaced.
Yellow: A Module was added previously but cannot be
detected now (i.e. Module removed).
Light blue: Serial number or module type is not matched
(i.e. an I/O Module has been replaced).
Background colour: This module is installed.
113
.
Replace>Select
Touchpoint Plus
Technical Handbook

Advertisement

Table of Contents
loading

Table of Contents