Honeywell Touchpoint Plus Technical Handbook page 141

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

Parameter Name
Alarm 2 Enable
Alarm 2 enable/disable
Alarm 2 Threshold
Alarm 2 trigger option (Rising or Falling)
Trigger
Alarm 2 Level
Alarm 2 threshold concentration
Alarm 3 Enable
Alarm 3 enable/disable
Alarm 3 Threshold
Alarm 3 trigger option (Rising or Falling)
Trigger
Alarm 3 Level
Alarm 3 threshold concentration
Gas Type
Gas type
The gas concentration within the dead band
Lower Zero Dead
limit will be suppressed to default base
Band
concentration. i.e. if the gas concentration is
between the (default base concentration
dead band) and (default base concentration +
Upper Zero Dead
upper dead band), then the reading will be the
Band
default base concentration.
Over-range gas concentration limit. This
Gas Over Range
parameter is used to generate over-range
Limit
warning.
Gas Under Range
Negative reading limit
Limit
Span Calibration
Target span gas concentration
Conc.
Bridge Current
Different value Depend on Detector
Unit Correction
Correction factor for other target gas
Factor
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Parameter
Description
lower
Configurable Parameter Reference Guide
Applies
Read/
Range
to
Write
mV Input
R/W
Disable/Enable
mV Input
R/W
Rising/Falling
mV Input
R/W
2~100%FS
mV Input
R/W
Disable/Enable
mV Input
R/W
Rising/Falling
mV Input
R/W
2~100%FS
mV Input
R/W
Flammable(2)
-20%FSD ~
mV Input
R/W
0%FSD
0%FSD ~
mV Input
R/W
20%FSD
100% ~
mV Input
R/W
105%FSD
mV Input
R/W
-24% ~ 0%FSD
mV Input
R/W
20 ~ 100 %FSD
mV Input
R/W
100~300mA
mV Input
R/W
1
141
Default Value
Remark
Disable
Rising
40% of Full range
Disable
Rising
60% of Full range
Depend on Gas Name
Flammable(2)
Toxic(0) O2(1) Flammable(2)
Flame(3)
Sensepoint ppm: -40%FSD ~
0
0%FSD
Sensepoint ppm: 0%FSD ~
40%FSD when the
0
measuring range is 0 –
10 %LEL
105 %FSD
-10 %FSD
50% of Full range
200 mA
1
Technical Handbook
Touchpoint Plus