Honeywell Touchpoint Plus Technical Handbook page 140

Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

Parameter Name
Target Gas Name
16 characters
Target Gas Unit
%, ppm, %LEL, %VOL, mA, User (6chars)
Target Gas Digit
Numbers of decimal point
Target Resolution
Resolution
Inhibit Time-out
Inhibit Time-out
Alarm will be continued until manual user
Alarm Latch
reset if latching is enabled.
Calibration Interval
0, 30 to 365
Target Full Range
1, 100, 1000, 10000, User
Alarm hysteresis is to avoid the alarm from
Threshold Alarm
frequent on/off when the gas reading is
Hysteresis
close to the alarm threshold.
Alarm 1 Enable
Alarm 1 enable/disable
Alarm 1 Threshold
Alarm 1 trigger option (Rising or Falling)
Trigger
Alarm 1 Level
Alarm 1 threshold concentration
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Parameter
Description
Configurable Parameter Reference Guide
Applies
Read/
Range
to
Write
Alphanumeric
mV Input
R/W
Character
Range
Alphanumeric
mV Input
R/W
Character
Range
mV Input
R/W
0~3
mV Input
R/W
0.1
mV Input
R/W
0~60
mV Input
R/W
Disable/Enable
mV Input
R/W
0, 30 to 365
mV Input
R/W
100
mV Input
R/W
0~10
mV Input
R/W
Disable/Enable
mV Input
R/W
Rising/Falling
mV Input
R/W
2~100%FS
140
Default Value
Remark
Write available when:
16 chars
Detector Name- User
Detector
Write available when:
Detector Name- User
Detector
mg/m3, g/m3, %VOL,
%
ppm, %LEL, UEG,
Ratio, %LEL x M, ppm x m,
EG x m, %Vol x m, LEL.m,
LEL%.m, %V/V, mA, kppm,
oC, oF, %RH
1
Changed by full scale setting
0.01, 0.1, 0.2, 0.5, 1, 2, 5,
0.1
10, 20, 50, 100
10
0: Disable, minute
Enable
per channel
180
0: Disable
Write available when:
100
Detector Name- User
Detector
2% of Full range
Disable
Rising
20% of Full range
Technical Handbook
Touchpoint Plus