9.2

XML/PLC error messages

Note that if there are error messages, the ERR LED ("ER") of the reader flashes. You can
read the error using the XML or PLC error codes. As an alternative, you can also recognize
the error using the LED status display of the RF680R and RF685R readers as described in
the section "How the LED status display works (Page 471)".
The following table explains the XML/PLC error codes. Only the errors relevant to the RF600
readers are included in the PLC error codes (STEP 7). You can find all other error codes in
the corresponding Ident profile manual.
Table 9- 2
Error messages of the RF600 readers
"ER"
XML/
PLC block
LED
LED
(hex)
(hex)
2 Hz
0x11
0xE1FE01
2 Hz
0x12
0xE1FE02
2 Hz
0x13
0xE1FE03
2 Hz
0x1A
0xE1FE0A
2 Hz
0x91
0xE1FE81
2 Hz
0x92
0xE1FE82
2 Hz
0x93
0xE1FE83
2 Hz
0x94
0xE1FE84
2 Hz
0x95
0xE1FE85
2 Hz
0x22
0xE2FE02
2 Hz
0xA1
0xE2FE81
2 Hz
0xA2
0xE2FE82
2 Hz
0xA3
0xE2FE83
SIMATIC RF600
System Manual, 06/2019, J31069-D0171-U001-A22-7618
Error description
Cannot write to the memory of the transponder.
Transponder memory is defective.
Transponder EEPROM was written too frequently and has reached the end of its ser-
vice life.
Presence error
The transponder is no longer within the transmission window of the reader. The command
was not or only partially executed.
Read command: There is no valid data in "IDENT_DATA".
Write command: The transponder that has just left the antenna field contains an incomplete
data record.
Possible causes:
Operating distance between reader and transponder is not being maintained.
Configuration error: The data record to be processed is too large (in dynamic mode).
Address error
The address area of the transponder has been exceeded.
Possible causes:
Start address of the command start has been incorrectly set.
Wrong transponder type
The area to be written to is write-protected.
The transponder is read/write-protected.
The transponder is not responding.
The transponder password is incorrect. Access is denied.
The verification of the written transponder data has failed.
General transponder error
The transponder has too little power to execute the command.
More transponders are located in the transmission window than can be processed at the
same time by the reader.
There is no transponder with the required EPC ID in the transmission window or there is no
transponder at all in the antenna field.
The requested data is not available.
CRC error in reader-transponder communication.
System diagnostics
9.2 XML/PLC error messages