System diagnostics
9.2 XML/PLC error messages
"ER"
XML/
PLC block
LED
LED
(hex)
(hex)
2 Hz
0x54
0xE5FE04
--
0x55
0xE5FE05
2 Hz
0x56
0xE5FE06
--
0x57
0xE5FE07
2 Hz
0x58
0xE5FE08
--
0x59
0xE5FE09
--
0x5A
0xE5FE0A
--
0x5B
0xE5FE0B
--
0x5C
0xE5FE0C
--
--
0xE5FE81
--
--
0xE5FE82
--
--
0xE5FE83
--
--
0xE5FE84
2 Hz
0x61
0xE6FE01
--
0x62
0xE6FE02
476
Error description
Invalid data block number (DBN) on the reader/communications module
Invalid data block number (DBN) in the Ident profile
Invalid data block length (DBL) on the reader/communications module
Invalid data block length (DBL) in the Ident profile
The previous command is still active or the buffer is full.
A new command was sent to the reader or communications module although the last com-
mand is still active.
The active command can only be aborted with "INIT".
Before a new command can be started, "DONE bit = 1" must be set (exception: "INIT").
Two Ident profile calls had the same "HW_ID", "CM_CHANNEL" and "LADDR" parame-
ter settings.
Two Ident profile calls are using the same pointer.
After eliminating the error, an "INIT" must be executed.
When working with command repetition (e.g., fixed code transponder), no data is being
fetched from the transponder. The data buffer on the reader/communications module
has overflowed. Transponder data has been lost.
The reader/communications module runs a hardware reset ("INIT_ACTIVE" set to "1"). The
Ident profile expects an "INIT" (bit 15 in the cyclic control word).
The "CMD" command code and the relevant acknowledgement do not match. This can be a
software error or synchronization error that cannot occur in normal operation.
Incorrect sequence of acknowledgement frames (TDB / DBN)
Synchronization error (incorrect increment of AC_H / AC_L and CC_H / CC_L in the cyclic
control word). "INIT" had to be executed.
Communications error between reader and communications module
Access denied
Communications error between reader and communications module
Resource is occupied
Communications error between reader and communications module
Functional error of the serial interface
Communications error between reader and communications module
Other faults/errors
Unknown command
An uninterpretable XML command was sent to the reader or the Ident profile sends an
uninterpretable command to the reader.
Possible causes:
The "AdvancedCmd" block was supplied with an incorrect "CMD".
The "CMD" input of the "AdvancedCmd" block was overwritten.
Invalid command index (CI)
System Manual, 06/2019, J31069-D0171-U001-A22-7618