5.4 S2 SYSTEM SETUP
The 745 provides a general purpose DC current input for use in monitoring any external parameter. Any stan-
dard transducer output may be connected to the analog input for monitoring.
S ANALOG INPUT
S [ENTER] for more
ANALOG INPUT NAME:

ANALOG INPUT

ANALOG INPUT UNITS:
µA
ANALOG INPUT RANGE:
0-1 mA
5
ANALOG INPUT MINIMUM
VALUE: 0 µA
ANALOG INPUT MAXIMUM
1000 µA
VALUE:
5-40
This message indicates the start of the ANALOG INPUT section. To continue
these setpoints press
EN TE R
Range: 18 alphanumeric characters
Press
to begin editing the name of the analog input. The text may be
E N TE R
changed from ANALOG INPUT one character at a time, using the
keys. Press the
V AL U E
next character position. This name will appear in the actual value message
A2 METERING/ANALOG INPUT.
Range: 6 alphanumeric characters
Enter the units of the quantity being read by editing the text as described
above. The 6 characters entered will be displayed instead of Units wherever
the analog input units are displayed.
Range: 0-1 mA / 0-5 mA / 4-20 mA / 0-20 mA
Select the current output range of the transducer that is connected to the
analog input.
Range: 0 to 65000 (steps of 1)
Enter the value of the quantity measured which corresponds to the minimum
output value of the transducer.
Range: 0 to 65000 (steps of 1)
Enter the value of the quantity measured which corresponds to the
maximum output value of the transducer.
745 Transformer Management Relay
5.4.9 ANALOG INPUT
, or press
to go to the next section.
M E SS AG E
key to store the edit and advance to the
E N TE R
GE Power Management
5 SETPOINTS
/
V ALU E