8 COMMUNICATIONS
Table 8–6: 745 MEMORY MAP (Sheet 49 of 57)
GROUP
ADDR
DESCRIPTION
(HEX)
WINDING 2
23D0
Winding 2 Current Demand Function
CURRENT
23D1
Winding 2 Current Demand Target
DEMAND
23D2
Winding 2 Current Demand Pickup
23D3
Winding 2 Current Demand Block
23D4
Reserved
23DF
Reserved
WINDING 3
23E0
Winding 3 Current Demand Function
CURRENT
23E1
Winding 3 Current Demand Target
DEMAND
23E2
Winding 3 Current Demand Pickup
23E3
Winding 3 Current Demand Block
23E4
Reserved
23EF
Reserved
XFORMER
23F0
Transformer Overload Function
OVERLOAD
23F1
Transformer Overload Target
23F2
Transformer Overload Pickup
23F3
Transformer Overload Delay
23F4
Transformer Overload Block
23F5
Transformer Overtemperature Alarm Signal
23F6
Reserved
23FF
Reserved
AGING
2400
Aging Factor Limit Function
FACTOR
2401
Aging Factor Limit Target
LIMIT
2402
Aging Factor Limit Pickup
2403
Aging Factor Limit Delay
2404
Aging Factor Limit Block
2405
Reserved
240F
Reserved
TAP CHANGER
2410
Tap Changer Failure Function
FAILURE
2411
Tap Changer Failure Target
2412
Tap Changer Failure Delay
2413
Tap Changer Failure Block
2414
Reserved
3FFF
Reserved
GE Power Management
RANGE
50 to 300
0 to 60000
1.1 to 10.0
0 to 60000
0 to 600.00
745 Transformer Management Relay
8.3 MODBUS MEMORY MAP
STEP
UNITS
FORMAT
VALUE
---
---
---
---
---
---
---
---
A
---
---
---
---
---
---
---
---
---
---
---
A
---
---
---
---
---
---
---
---
---
1
% rated
1
s
---
---
---
---
---
---
---
---
---
---
---
---
0.1
--
1
minutes
---
---
---
---
---
---
---
---
---
0.01
s
---
---
---
FACTORY
CODE
DEFAULT
F30
0 = Disabled
F46
0 = Self-reset
F79
400 A
F87
0 = Disabled
F30
0 = Disabled
F46
0 = Self-reset
F80
400 A
F87
0 = Disabled
F30
0 = Disabled
F46
0 = Self-reset
F1
208% rated
F1
10 s
F87
0 = Disabled
F88
0 = Disabled
F30
0 = Disabled
F46
0 = Self-reset
F2
20 = 2.0
F1
10 minutes
F87
0 = Disabled
8
F30
0 = Disabled
F46
0 = Self-reset
F3
500 = 5.00 s
F87
0 = Disabled
8-65