11 SETPOINT TABLES
Table 11–6: S4 ELEMENTS (Sheet 2 of 12)
DESCRIPTION
5th Harmonic Inhibit Level
INSTANTANEOUS DIFFERENTIAL
Inst. Differential Function
Inst. Differential Target
Inst. Differential Pickup
Inst. Differential Block
PHASE OVERCURRENT
W1 Phase Time O/C Function
W1 Phase Time O/C Target
W1 Phase Time O/C Pickup
W1 Phase Time O/C Shape
W1 Phase Time O/C Multiplier
W1 Phase Time O/C Reset
W1 Phase Time O/C Block
W1 Phase Time O/C Harm Derating
W2 Phase Time O/C Function
W2 Phase Time O/C Target
W2 Phase Time O/C Pickup
W2 Phase Time O/C Shape
W2 Phase Time O/C Multiplier
W2 Phase Time O/C Reset
W2 Phase Time O/C Block
W2 Phase Time O/C Harm Derating
W3 Phase Time O/C Function
W3 Phase Time O/C Target
W3 Phase Time O/C Pickup
W3 Phase Time O/C Shape
W3 Phase Time O/C Multiplier
W3 Phase Time O/C Reset
W3 Phase Time O/C Block
W3 Phase Time O/C Harm Derating
W1 Phase Inst O/C 1 Function
W1 Phase Inst O/C 1 Target
W1 Phase Inst O/C 1 Pickup
W1 Phase Inst O/C 1 Delay
GE Power Management
DEFAULT
GROUP 1
10.0% ƒo
Enabled
Latched
8.00 x CT
Disabled
Enabled
Latched
1.20 x CT
Ext Inverse
1.00
Linear
Disabled
Disabled
Enabled
Latched
1.20 x CT
Ext Inverse
1.00
Linear
Disabled
Disabled
Enabled
Latched
1.20 x CT
Ext Inverse
1.00
Linear
Disabled
Disabled
Enabled
Latched
10.00 x CT
0 ms