Output Relays - GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

5.7 S5 OUTPUTS
This section contains the settings (including the FlexLogic™ equation) to configure output relays 1 to 8.
S OUTPUT RELAYS
S [ENTER] for more
S OUTPUT RELAY 1
S [ENTER] for more
OUTPUT 1 NAME:
Solid State Trip
OUTPUT 1 OPERATION:
Self-resetting
5
OUTPUT 1 TYPE:
Trip
OUTPUT 1 FLEXLOGIC
01: Percent Diff OP
Table 5–8: OUTPUT RELAY DEFAULT FLEXLOGIC
FLEXLOGIC
GATE
1 to 3
01
Percent Diff OP
02
Inst Diff OP
03
Any W1 OC OP
04
Any W2 OC OP
05
OR (4 inputs)
06 to 20
END
5-84
This message indicates the start of the OUTPUT RELAYS section. To continue
these setpoints press
This message indicates the start of the OUTPUT RELAY 1 (2-8) section. To
continue these setpoints press
Range: 18 alphanumeric characters
Press
edit the name of the output. The text may be changed from
E N TE R
Solid State Trip one character at a time, using the
Press
to store the edit and advance to the next character position.
E N TE R
Range: Self-resetting / Latched
Select Latched to maintain the Output 1 (2-8) contacts in the energized state,
even after the condition that caused the contacts to operate is cleared, until
a reset command is issued (or automatically after one week). Select Self-
reset to automatically de-energize the contacts after the condition is cleared.
The solid state output (Output 1) remains closed until externally reset by a
momentary interruption of current, unless wired in parallel with an
electromechanical relay (Outputs 2-8) in which case it turns off when the
relay operates.
Range: Trip / Alarm / Control
Select Trip to turn the TRIP indicator on or Alarm to turn the ALARM indicator
on when this output operates. Otherwise, select Control .
Note that the TRIP indicator remains on until a reset command is issued (or
automatically after one week). The ALARM indicator turns off automatically
when the output is no longer operated.
Range: any FlexLogic™ input or gate
The 20 messages shown in the table below are the parameters of the
FlexLogic™ equation for Output 1 (2-8) as described in the introduction to
FlexLogic™.
OUTPUT RELAY NUMBER
4
5
Volts/Hertz 1 OP
W1 THD Level OP
Volts/Hertz 2 OP
W2 THD Level OP
OR (2 inputs)
Xfmr Overload OP
END
5th HarmLevel OP
END
OR (4 inputs)
END
END
745 Transformer Management Relay
or press
for the next section.
EN TE R
M E SSA G E
or press
E N TE R
M E SSA G E
6
Underfreq 1 OP
Underfreq 2 OP
Freq Decay R1 OP
Freq Decay R2 OP
OR (2 inputs)
OR (2 inputs)
END
END
END
5 SETPOINTS

5.7.4 OUTPUT RELAYS

for the next section.
/
: keys.
V AL U E
V AL U E
7
8
Freq Decay 3 OP
END
END
END
END
END
END
END
END
GE Power Management