GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual page 377

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

11 SETPOINT TABLES
Table 11–6: S4 ELEMENTS (Sheet 4 of 12)
DESCRIPTION
W2 Ntrl Time O/C Target
W2 Ntrl Time O/C Pickup
W2 Ntrl Time O/C Shape
W2 Ntrl Time O/C Multiplier
W2 Ntrl Time O/C Reset
W2 Ntrl Time O/C Block
W3 Ntrl Time O/C Function
W3 Ntrl Time O/C Target
W3 Ntrl Time O/C Pickup
W3 Ntrl Time O/C Shape
W3 Ntrl Time O/C Multiplier
W3 Ntrl Time O/C Reset
W3 Ntrl Time O/C Block
W1 Ntrl Inst O/C 1 Function
W1 Ntrl Inst O/C 1 Target
W1 Ntrl Inst O/C 1 Pickup
W1 Ntrl Inst O/C 1 Delay
W1 Ntrl Inst O/C 1 Block
W2 Ntrl Inst O/C 1 Function
W2 Ntrl Inst O/C 1 Target
W2 Ntrl Inst O/C 1 Pickup
W2 Ntrl Inst O/C 1 Delay
W2 Ntrl Inst O/C 1 Block
W3 Ntrl Inst O/C 1 Function
W3 Ntrl Inst O/C 1 Target
W3 Ntrl Inst O/C 1 Pickup
W3 Ntrl Inst O/C 1 Delay
W3 Ntrl Inst O/C 1 Block
W1 Ntrl Inst O/C 2 Function
W1 Ntrl Inst O/C 2 Target
W1 Ntrl Inst O/C 2 Pickup
W1 Ntrl Inst O/C 2 Delay
W1 Ntrl Inst O/C 2 Block
W2 Ntrl Inst O/C 2 Function
W2 Ntrl Inst O/C 2 Target
GE Power Management
DEFAULT
GROUP 1
Latched
0.85 x CT
Ext Inverse
1.00
Linear
Disabled
Disabled
Latched
0.85 x CT
Ext Inverse
1.00
Linear
Disabled
Enabled
Latched
10.00 x CT
0 ms
Disabled
Disabled
Latched
10.00 x CT
0 ms
Disabled
Disabled
Latched
10.00 x CT
0 ms
Disabled
Disabled
Latched
10.00 x CT
0 ms
Disabled
Disabled
Latched
745 Transformer Management Relay
11.1 COMMISSIONING SUMMARY
GROUP 2
GROUP 3
GROUP 4
11
11-9

Advertisement

Table of Contents
loading

Table of Contents