Analog Input; Power - GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

6 ACTUAL VALUES
The 745 provides the ability to monitor any external quantity via an auxiliary current input called the ANALOG
INPUT.
S ANALOG INPUT
S [ENTER] for more

ANALOG INPUT:

0 µA
The 745 calculates and displays real, reactive, and apparent power as well as the power factor for all of the
available windings providing that the voltage sensing is enabled. Power flowing into the power transformer is
designated as source power and power flowing out of the transformer is designated as load power.
S POWER
S [ENTER] for more
The following Actual Values messages are repeated for Windings 1, 2 and 3.
S W1 POWER
S [ENTER] for more
W1 REAL POWER:
0 MW
W1 REACTIVE POWER:
0 Mvar
W1 APPARENT POWER:
0 MVA
W1 POWER FACTOR:
0.00
GE Power Management
This message indicates the start of the Analog Input actual values. To view
these actual values press
This message displays the scaled value of the analog input, as defined by
the setpoints noted above. In this message, the name programmed in
S2 SYSTEM SETUP/ANALOG INPUT/ANALOG INPUT NAME is displayed instead of
ANALOG INPUT (the factory default), and the units programmed in
S2 SYSTEM SETUP/ANALOG INPUT/ANALOG INPUT UNITS are displayed instead
of µA (which is the factory default).
This message indicates the start of the Power actual values. To view these
actual values press
E N TE R
This message indicates the start of the Power actual values. To view these
actual values press
E N TE R
This message displays the total 3 phase real power (in MW) for winding 1(2/
3) as source or load.
This message displays the total 3 phase reactive power (in Mvar) for winding
1(2/3) as source or load.
This message displays the total 3 phase apparent power (in MVA) for
winding 1(2/3).
This message displays the total 3 phase power factor (as lead or lag) for
winding 1(2/3).
745 Transformer Management Relay
6.3.10 ANALOG INPUT
or press
for the end of page A2.
E N TE R
M E SSA G E
or press
for the end of page A2.
M E SSA G E
or press
for the end of page A2.
M E SSA G E
6.3 A2 METERING

6.3.11 POWER

6
6-11

Advertisement