Current Demand; Ambient Temperature; Loss Of Life - GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

6.3 A2 METERING
b) CURRENT DEMAND
The following Actual Values messages are repeated for Windings 1, 2 and 3.
S W1 CURRENT DEMAND
S [ENTER] for more
W1 PHASE A CURRENT
DEMAND:
0A
W1 PHASE B CURRENT
DEMAND:
0A
W1 PHASE C CURRENT
DEMAND:
0A
MAXIMUM W1 DEMAND:
0A in phase A
MAXIMUM W1 DEMAND
DATE: Jan 01 1996
MAXIMUM W1 DEMAND
TIME: 00:00:00.000
Ambient temperature is monitored via an RTD connected to the 745.
6
S AMBIENT TEMP
S [ENTER] for more

AMBIENT TEMPERATURE

0 °C
S LOSS OF LIFE
S [ENTER] for more
HOTTEST-SPOT WINDING
TEMPERATURE:
INSULATION AGING
FACTOR:
TOTAL ACCUM LOSS OF
LIFE:
0.00 hours
6-10
This message indicates the start of the Winding 1 (2/3) Current Demand
actual values. To view these actual values press
scroll to the current demand values for the next winding.
This message displays the Winding 1 (2/3) phase A current demand.
This message displays the Winding 1 (2/3) phase B current demand.
This message displays the Winding 1 (2/3) phase C current demand.
This message displays the maximum Winding 1 (2/3) current demand and
the phase in which it occurred since the demand data was last reset.
This message displays the date when the maximum Winding 1 (2/3) current
demand was detected. If the date has never been programmed, this
message will display Jan 01 1996
This message displays the time when the maximum Winding 1 (2/3) current
demand was detected.
This message indicates the start of the Ambient Temperature actual values.
To view these actual values press
section.
This message displays the measured ambient temperature.
This message indicates the start of the LOSS OF LIFE actual values. To
view these actual values press
This is the computed hottest-spot temperature, based on the ambient
temperature and the highest-load winding current.
1ºC
The insulation aging factor is computed from the hottest-spot temperature.
0.0
Total equivalent service hours of the transformer.
745 Transformer Management Relay
6 ACTUAL VALUES
or press
EN TE R
6.3.8 AMBIENT TEMPERATURE
or press
EN TE R
M E SS AG E

6.3.9 LOSS OF LIFE

or press
for the next section.
E N TE R
M E SS AG E
GE Power Management
to
M E SSA G E
for the next