5.7 S5 OUTPUTS
Protection and monitoring elements already have their own programmable delay timers, where they are
required. For additional flexibility, 10 independent timers are available for implementing custom schemes
where timers are not available. For example, a pickup delay timer may be required on a logic input; or, a single
delay timer may be required on the output of a block of logic.
This section contains the settings to configure timers 1 to 10.
S TIMERS
S [ENTER] for more
TIMER 1 (2-10)
S TIMER 1
S [ENTER] for more
TIMER 1 START:
END
TIMER 1 PICKUP
DELAY: 0.00 s
5
TIMER 1 DROPOUT
DELAY: 0.00 s
5-86
This message indicates the start of the TIMERS section. To continue these
setpoints press
or press
EN TE R
This message indicates the start of the TIMER 1 (2-10) section. To continue
these setpoints press
EN TE R
Range: any FlexLogic input.
Select the FlexLogic entry which, when operated or asserted, will start timer
1 (2-10).
Range: 0.00 to 600.00 (steps of 0.01)
Enter the delay time during which the start condition for timer 1 (2-10) must
remain operated or asserted, before the timer will operate.
Range: 0.00 to 600.00 (steps of 0.01)
Enter the delay time after which the start condition for timer 1 (2-10) must
remain not operated or not asserted, before the timer will stop operating.
745 Transformer Management Relay
for the next section.
M E SS AG E
or press
for the next section.
M E SSA G E
GE Power Management
5 SETPOINTS

5.7.7 TIMERS