Scratchpad; Installation - GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

5.3 S1 745 SETUP
Up to 5 message screens can be programmed and selected as default messages. These messages can be
used to provide identification information about the system or instructions to operators. User text messages
can be entered as follows:
S SCRATCHPAD
S [ENTER] for more
Text 1
S INSTALLATION
S [ENTER] for more
745 SETPOINTS:
5
Not Programmed
5-30
Use these setpoints to enter up to 5 user programmable messages to be
displayed with the list of default messages. To continue setting the user
messages press the
E N TE R
section.
Range: 40 alphanumeric characters
Press
to begin editing scratchpad message 1 (2-5). The text may be
E N TE R
changed from Text 1 one character at a time, using
the
key to store the edit and advance to the next character position.
E N TE R
This message may then be stored as a default message.
This message indicates the start of the INSTALLATION section. To continue
these setpoints press
EN TE R
Range: Not Programmed / Programmed
In order to safeguard against the installation of a relay whose setpoints have
not been entered, the 745 will not allow signaling of any output relay, will
have the IN SERVICE indicator off and the SELF-TEST ERROR indicator
on, until the 745 is set to Programmed. The setpoint is defaulted to Not
Programmed when the relay leaves the factory. The following self-test error
message is displayed automatically until the 745 is put into the programmed
state:
S SETPOINTS HAVE NOT
S BEEN PROGRAMMED
745 Transformer Management Relay
key, or press the
M E SS AG E
V AL U E

5.3.10 INSTALLATION

, or press
to go to the next section.
M E SS AG E
GE Power Management
5 SETPOINTS

5.3.9 SCRATCHPAD

key to go to the next
/
. Press
V ALU E