GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual page 82

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

5.3 S1 745 SETUP
S UPGRADE OPTIONS
S [ENTER] for more
ENABLE ANALOG I/O?
No
ENABLE LOSS OF LIFE?
No
ENABLE RESTRICTED
GROUND FAULT? No
ENTER PASSCODE:
5
UPGRADE UPTIONS?
No
5-32
This message indicates the start of the UPGRADE OPTIONS section. To
continue with these setpoints press
previous section.
Range: No / Yes
Select Yes if the upgrade options set supports the Analog I/O feature,
otherwise select No. The default value for this setpoint reflects the current
state of the option.
Range: No / Yes
Select Yes if the upgrade options set supports the Loss Of Life feature and
select No otherwise. The default value for this setpoint reflects the current
state of the option.
Range: No / Yes
Select Yes if the upgrade options set supports the Restricted Ground Fault
feature and select No otherwise. The default value for this setpoint reflects
the current state of the option.
Range: 16 hexadecimal characters [0 to 9 and A to F]
Press
to begin entering the factory-supplied upgrade passcode. This
E N TE R
setpoint has a textual format, thus it is edited in the same manner as, for
example, the setpoints under S1 745 SETUP/SCRATCHPAD.
Range: No / Yes
When all of the above setpoints are properly programmed, select Yes and
press
to prompt the 745 to upgrade its options. A flash message
EN TE R
appears indicating the results of the upgrade. A successful upgrade may be
verified by examining the installed options display under A4 PRODUCT INFO/
REVISION CODES/INSTALLED OPTIONS.
745 Transformer Management Relay
5 SETPOINTS
5.3.12 UPGRADE OPTIONS
, or press
to go to the
E N TE R
M E SSA G E