11.1 COMMISSIONING SUMMARY
Table 11–6: S4 ELEMENTS (Sheet 7 of 12)
11
DESCRIPTION
W2 Rstd Gnd Fault Slope
W2 Rstd Gnd Fault Delay
W2 Rstd Gnd Fault Block
W3 Rstd Gnd Fault Function
W3 Rstd Gnd Fault Target
W3 Rstd Gnd Fault Pickup
W3 Rstd Gnd Fault Slope
W3 Rstd Gnd Fault Delay
W3 Rstd Gnd Fault Block
W1 Rst Gnd Inst O/C Function
W1 Rst Gnd Inst O/C Target
W1 Rst Gnd Inst O/C Pickup
W1 Rst Gnd Inst O/C Delay
W1 Rst Gnd Inst O/C Block
W2 Rst Gnd Inst O/C Function
W2 Rst Gnd Inst O/C Target
W2 Rst Gnd Inst O/C Pickup
W2 Rst Gnd Inst O/C Delay
W2 Rst Gnd Inst O/C Block
W3 Rst Gnd Inst O/C Function
W3 Rst Gnd Inst O/C Target
W3 Rst Gnd Inst O/C Pickup
W3 Rst Gnd Inst O/C Delay
W3 Rst Gnd Inst O/C Block
NEGATIVE SEQUENCE OVERCURRENT
W1 Neg Seq Time O/C Function
W1 Neg Seq Time O/C Target
W1 Neg Seq Time O/C Pickup
W1 Neg Seq Time O/C Shape
W1 Neg Seq Time O/C Multiplier
W1 Neg Seq Time O/C Reset
W1 Neg Seq Time O/C Block
W2 Neg Seq Time O/C Function
W2 Neg Seq Time O/C Target
W2 Neg Seq Time O/C Pickup
11-12
DEFAULT
GROUP 1
10%
0.10 s
Disabled
Disabled
Latched
0.08 x CT
10%
0.10 s
Disabled
Disabled
Latched
10.00 x CT
0 ms
Disabled
Disabled
Latched
10.00 x CT
0 ms
Disabled
Disabled
Latched
10.00 x CT
0 ms
Disabled
Disabled
Latched
0.25 x CT
Ext Inverse
1.00
Linear
Disabled
Disabled
Latched
0.25 x CT
745 Transformer Management Relay
11 SETPOINT TABLES
GROUP 2
GROUP 3
GROUP 4
GE Power Management
Need help?
Do you have a question about the 745 TRANSFORMER MANAGEMENT RELAY and is the answer not in the manual?
Questions and answers