GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual page 267

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

8 COMMUNICATIONS
Table 8–6: 745 MEMORY MAP (Sheet 41 of 57)
GROUP
ADDR
DESCRIPTION
(HEX)
WINDING 1
21C4
Winding 1 Ground Inst O/C 2 Block
GROUND INST
21C5
Reserved
OC 2
continued
21CF
Reserved
WINDING 2
21D0
Winding 2 Ground Inst O/C 2 Function
GROUND INST
21D1
Winding 2 Ground Inst O/C 2 Target
O/C 2
21D2
Winding 2 Ground Inst O/C 2 Pickup
21D3
Winding 2 Ground Inst O/C 2 Delay
21D4
Winding 2 Ground Inst O/C 2 Block
21D5
Reserved
21DF
Reserved
WINDING 3
21E0
Winding 3 Ground Inst O/C 2 Function
GROUND INST
21E1
Winding 3 Ground Inst O/C 2 Target
O/C 2
21E2
Winding 3 Ground Inst O/C 2 Pickup
21E3
Winding 3 Ground Inst O/C 2 Delay
21E4
Winding 3 Ground Inst O/C 2 Block
21E5
Reserved
21EF
Reserved
WINDING 1
21F0
Winding 1 Restricted Ground Fault Function
RESTD GND
21F1
Winding 1 Restricted Ground Fault Target
FAULT
21F2
Winding 1 Restricted Ground Fault Pickup
21F3
Winding 1 Restricted Ground Fault Slope
21F4
Winding 1 Restricted Ground Fault Delay
21F5
Winding 1 Restricted Ground Fault Block
21F6
Reserved
21FF
Reserved
WINDING 2
2200
Winding 2 Restricted Ground Fault Function
RESTD GND
2201
Winding 2 Restricted Ground Fault Target
FAULT
2202
Winding 2 Restricted Ground Fault Pickup
2203
Winding 2 Restricted Ground Fault Slope
2204
Winding 2 Restricted Ground Fault Delay
2205
Winding 2 Restricted Ground Fault Block
2206
Reserved
220F
Reserved
GE Power Management
RANGE
0.05 to 20.00
0 to 60000
0.05 to 20.00
0 to 60000
0.05 to 20.00
0 to 100
0.00 to 600.00
0.05 to 20.00
0 to 100
0.00 to 600.00
745 Transformer Management Relay
8.3 MODBUS MEMORY MAP
STEP
UNITS
FORMAT
VALUE
---
---
---
---
---
---
---
---
---
× CT
0.01
1
ms
---
---
---
---
---
---
---
---
---
× CT
0.01
1
ms
---
---
---
---
---
---
---
---
---
× CT
0.01
1
%
0.01
s
---
---
---
---
---
---
---
---
---
× CT
0.01
1
%
0.01
s
---
---
---
FACTORY
CODE
DEFAULT
F87
0 = Disabled
F30
0 = Disabled
F46
1 = Latched
1000=10.00 × CT
F3
F1
0 ms
F87
0 = Disabled
F30
0 = Disabled
F46
1 = Latched
1000=10.00 × CT
F3
F1
0 ms
F87
0 = Disabled
F30
0 = Disabled
F46
1 = Latched
8 = 0.08 × CT
F3
F1
10%
F3
10 = 0.10 s
F87
0 = Disabled
8
F30
0 = Disabled
F46
1 = Latched
8 = 0.08 × CT
F3
F1
10%
F3
10 = 0.10 s
F87
0 = Disabled
8-57

Advertisement

Table of Contents
loading

Table of Contents