8.4 DNP COMMUNICATIONS

8.4 DNP COMMUNICATIONS
DNP 3.0

DEVICE PROFILE DOCUMENT

Vendor Name: General Electric Power Management Inc.
Device Name: 745 Transformer Management Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Analog Input (Object 30, Variations 1, 2, 3 and 4)
Analog Input Change (Object 32, Variations 1, 2, 3 and 4)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Data Link Re-tries:
Ë
None
Ë
Fixed

5
Configurable (Note 1)
Requires Data Link Layer Confirmation:
Ë
Never
Ë
Always
Ë
Sometimes

5
Configurable (Note 1)
Requires Application Layer Confirmation:
Ë Never
Ë Always

5
When reporting Event Data
Ë When sending multi-fragment responses
Ë Sometimes
Ë Configurable
Timeouts while waiting for:
8
Data Link Confirm
Complete Appl. Fragment
Application Confirm
Complete Appl. Response
Others:
8-92
Device Function:
Ë Master
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Application Layer Re-tries:

5
Ë Configurable
Ë None
Ë Fixed
Ë Variable

5
Ë Fixed
Ë Variable Ë Configurable
None

5
Ë Fixed
Ë Variable Ë Configurable
None

5
Ë Fixed
Ë Variable Ë Configurable
None
(None)
745 Transformer Management Relay
8.4.1 DEVICE PROFILE DOCUMENT

5
Slave
None

5
Configurable (Note 1)
GE Power Management