2.42.2 Setting Hints

General
Settings on the
Protection Device
7UM62 Manual
C53000-G1176-C149-3
9011A RTD 1 TYPE
Temperature
Non-linear-
calculation
ized values
Figure 2-129 Logic Diagram of the Temperature Evaluation
The temperature detection function is only effective and accessible if it has been as-
signed to an interface during the configuration of the protection functions (Section
2.2.1). Address 0190 RTD-BOX INPUT is used to allocate the thermobox(es) to the
interface (e.g. interface C) through which it will be operated. The number of detector
inputs and the communication mode are selected with address 0191 RTD CONNEC-
TION. The temperature unit (°C or °F) has been set in Power System Data 1 at ad-
dress 0276 TEMP. UNIT.
The settings to be made on the protection device are the same for each input; they are
described here as an example for measuring input 1.
For RTD1 (temperature detector for measuring 1), the type of temperature detector is
set at address 9011A RTD 1 TYPE. Setting options are Pt 100 W, Ni 120 W and
Ni 100 W. Where no measuring point is provided for RTD1, RTD 1 TYPE = Not
connected is set. This setting is only possible with DIGSI
rameters".
Temperature Detection by Thermoboxes
9013 RTD 1 STAGE 1
9015 RTD 1 STAGE 2
Monitoring
®
RTD 1 St.1 p.up
14112
FNo.
RTD 1 St.2 p.up
14113
FNo.
Fail: RTD 1
14111
FNo.
≥1
Fail: RTD
14101
FNo.
Fail: RTD-Box 1
00264
FNo.
4 under „Advanced Pa-
271