Siemens Siprotec 7UM62 Manual page 106

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Functions
Tripping
Characteristic
90
The parameters for the tripping characteristic are set at the addresses 2021 through
2044A. The meaning of the parameters is shown in Figure 2-43. The numerical values
at the branches are the parameter addresses.
Address 2021 I-DIFF> is the pickup value for the differential current. The pickup value
is referred to the nominal current of the generator or motor. For generators and
motors, a setting between 0.1 and 0.2 is recommended.
In addition to the pickup threshold I-DIFF>, a second pickup threshold is considered.
When this threshold (2031 I-DIFF>>) is exceeded, a trip signal is issued regardless
of the magnitude of the stabilizing current (non-stabilized high-speed tripping). This
stage must be set higher than I-DIFF>. Recommendation: Set a value above the
steady-state value of the transient short-circuit current, i.e.:.
I-DIFF>>
With values for x
' between 0.15 and 0.35, the resulting setting values for IDIFF>> are
d
approx. (3 to 7) ⋅ I
N, Generator
The tripping characteristic has two more branches (Figure 2-43). Address 2041A
SLOPE 1 determines the slope of the first branch, whose starting point is specified in
the parameter 2042A BASE POINT 1. This branch considers current-proportional
error currents. These are mainly transformation errors of the main CTs and of the input
CTs. If the CTs are identical, the default setting of 0.25 can be reduced to 0.15.
The second branch produces a higher stabilization in the range of high currents which
may lead to current transformer saturation. Its base point is set at address 2044A
BASE POINT 2. The slope is set at address 2043A SLOPE 2. The stability of the
relay during current transformer saturation can be influenced by this parameter. A
higher slope results in a higher stability. The default setting of 0.5 has proven to be a
good value.
I
diff
10
---------------
I
NObj
9
8
2031
I–DIFF>>
7
6
5
4
3
2
b
1
a
2021
I–DIFF>
1
2
3
2044
BASE POINT 2
2042
2056
BASE POINT 1
EXF–STAB
Figure 2-43
Parameters Determining the Shape of the Tripping Characteristic
1
>
------ I
N, Generator
x'
d
.
Trip area
4
5
6
7
8
9
Block area
2043
SLOPE 2
c
Add-on stabilization
10 11 12 13 14 15 16 17 18
C53000-G1176-C149-3
d
2041
SLOPE 1
I
stab
---------------
I
NObj
7UM62 Manual

Advertisement

Table of Contents
loading