Note:
The jumper settings must correspond to the mode set at addresses 0295, 0296 (volt-
age or current input) and 0297 (with/without filter). If they do not, the device is blocked
and outputs an alarm. After any changes to the jumper settings, you should therefore
immediately change the corresponding parameter settings using DIGSI
Jumpers X71, X72 and X73 on the I/O-6 board are used to set the bus address and
must not be changed. Table 3-17 shows the factory setting of the jumpers.
Table 3-17
Factory Jumper Setting on the I/O-6 Board
Jumper
Factory Setting
X71 (AD0)
X72 (AD1)
X73 (AD2)
Note:
Measuring transducers that are not used should be shorted at the input terminals.
1–2 (H)
2–3 (L)
1–2 (H)
3.1 Installation and Connections
®
4.
331