Functional Scope; Description; Setting Hints - Siemens Siprotec 7UM62 Manual

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Functions
2.2

Functional Scope

2.2.1

Description

General
Determination of
Functional Scope
2.2.2

Setting Hints

Special Cases
18
The 7UM62 has numerous protective and additional functions. The hardware and
firmware provided is designed for this scope of functions. Nevertheless a few
restrictions apply to the use of the earth fault current and earth fault voltage inputs U
and I
respectively. It is not possible to feed different measured quantities to one and
EE
the same input, i.e. to use the input, for example, for both rotor and stator earth fault
protection. Table 2-2 gives an overview of the protective functions and the inputs they
use.
The command functions can be matched to the plant conditions. In addition, individual
functions can be activated or deactivated during the configuration procedure, so that
functions that are not needed can be disabled.
The available protective and additional functions can be configured as Enabled or
Disabled. For individual functions, the choice between several alternatives may be
presented, as described below.
Functions that are configured as Disabled are not processed by the 7UM62: There
are no messages, and corresponding settings (functions, limit values) are not
displayed during detailed settings.
Note:
The functions and default settings depend of the variant ordered (for details refer to
Table 2-1 and Appendix A.1). Also, not all combinations of protective functions are
possible because of certain restrictions imposed by the hardware (see Table 2-2,
"Allocation of Device Inputs to Protection Functions").
Configuration settings may be entered using a PC and the software program DIGSI
and transferred via the operator interface on the device front, or via the rear serial
service interface. Operation is described in the SIPROTEC
Entry of password No. 7 (for setting modification) is required to modify configuration
settings. Without the password, the settings may be read, but cannot be modified and
transmitted to the device.
The functional scope with the available options is set in the Device Configuration
dialog box to match plant requirements.
Most settings are self-explanatory. The special cases are described below.
If the setting group change-over function is to be used, the setting in address 0103
Grp Chge OPTION must be set to enabled. In this case, it is possible to apply two
groups of settings for the function parameters (refer also to Section 2.4) so that a
convenient and fast switch-over between these setting groups is possible. The setting
Disabled implies that only one function parameter setting group can be applied and
used.
®
®
4 System Manual.
7UM62 Manual
C53000-G1176-C149-3