Siemens Siprotec 7UM62 Manual page 556

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

A Appendix
Addr.
Setting Title
7201
DC PROTECTION
7202
MEAS.METHOD
7203
DC >/<
7204
U DC ><
7205
I DC ><
7206
T DC
7301
20 mA (B1) =
7302
MIN VALUE (B1)
7303
20 mA (B2) =
7304
MIN VALUE (B2)
7305
20 mA (D1) =
7306
MIN VALUE (D1)
7307
20 mA (D2) =
7308
MIN VALUE (D2)
8001
FUSE FAIL MON.
8101
MEASURE.
SUPERV
8102
BALANCE U-LIMIT Measurement
8103
BAL. FACTOR U
8104
BAL. I LIMIT S1
8105
BAL. FACT. I S1
8106
BAL. I LIMIT S2
540
Function
Setting Options
DC Voltage/
OFF
Current Protec-
ON
tion
Block relay for trip
commands
DC Voltage/
Mean Value
Current Protec-
Root Mean Square
tion
DC Voltage/
DC Voltage/Current
Current Protec-
Stage DC >
tion
DC Voltage/Current
Stage DC <
DC Voltage/
0.1..8.5 V
Current Protec-
tion
DC Voltage/
0.2..17.0 mA
Current Protec-
tion
0.00..60.00 sec; ∞
DC Voltage/
Current Protec-
tion
Analog Outputs 10.0..1000.0 %
Analog Outputs 0.0..5.0 mA
Analog Outputs 10.0..1000.0 %
Analog Outputs 0.0..5.0 mA
Analog Outputs 10.0..1000.0 %
Analog Outputs 0.0..5.0 mA
Analog Outputs 10.0..1000.0 %
Analog Outputs 0.0..5.0 mA
Supervision
OFF
ON
Measurement
OFF
Supervision
ON
10..100 V
Supervision
Measurement
0.58..0.90
Supervision
Measurement
0.10..1.00 A
Supervision
Measurement
0.10..0.90
Supervision
Measurement
0.10..1.00 A
Supervision
Default Setting
OFF
DC Voltage/Current Protec-
tion
Mean Value
Measurement Method
(MEAN/RMS Values)
DC Voltage/Current
Method of Operation (DC >/
Stage DC >
<)
2.0 V
DC Voltage Pickup
4.0 mA
DC Current Pickup
2.00 sec
Time Delay for Trip of DC
Protection
200.0 %
20 mA (B1) correspond to
1.0 mA
Output value (B1) valid
from
200.0 %
20 mA (B2) correspond to
1.0 mA
Output value (B2) valid
from
200.0 %
20 mA (D1) correspond to
1.0 mA
Output value (D1) valid
from
200.0 %
20 mA (D2) correspond to
1.0 mA
Output value (D2) valid
from
OFF
Fuse Failure Monitor
OFF
Measurement Supervision
50 V
Voltage Threshold for
Balance Monitoring
0.75
Balance Factor for Voltage
Monitor
0.50 A
Current Balance Monitor
Side 1
0.50
Balance Factor for Current
Monitor S1
0.50 A
Current Balance Monitor
Side 2
Comments