Siemens Siprotec 7UM62 Manual page 559

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Addr.
Setting Title
8511
MEAS. VALUE 6<
8512
THRESHOLD
MV6<
8601
EXTERN TRIP 1
8602
T DELAY
8701
EXTERN TRIP 2
8702
T DELAY
8801
EXTERN TRIP 3
8802
T DELAY
8901
EXTERN TRIP 4
8902
T DELAY
9011A RTD 1 TYPE
9012A RTD 1 LOCATION
7UM62 Manual
C53000-G1176-C149-3
Function
Setting Options
Threshold
Disabled
supervision
Active Power P
Reactive Power Q
Change of Active
Power Delta P
Positive Sequence
Voltage U1
Negative Sequence
Voltage U2
Zero Sequence Cur-
rent I0
Positive Sequence
Current I1
Negative Sequence
Current I2
Power Angle PHI
Threshold
-200..200 %
supervision
External Trip
OFF
Functions
ON
Block relay for trip
commands
0.00..60.00 sec; ∞
External Trip
Functions
External Trip
OFF
Functions
ON
Block relay for trip
commands
0.00..60.00 sec; ∞
External Trip
Functions
External Trip
OFF
Functions
ON
Block relay for trip
commands
0.00..60.00 sec; ∞
External Trip
Functions
External Trip
OFF
Functions
ON
Block relay for trip
commands
0.00..60.00 sec; ∞
External Trip
Functions
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Default Setting
Disabled
Measured Value for Thres-
hold MV6<
100 %
Pickup Value of Measured
Value MV6<
OFF
External Trip Function 1
1.00 sec
Ext. Trip 1 Time Delay
OFF
External Trip Function 2
1.00 sec
Ext. Trip 2 Time Delay
OFF
External Trip Function 3
1.00 sec
Ext. Trip 3 Time Delay
OFF
External Trip Function 4
1.00 sec
Ext. Trip 4 Time Delay
Pt 100 Ohm
RTD 1: Type
Winding
RTD 1: Location
A.12 Settings
Comments
543