Sensitive Earth Fault Protection (Ansi 51Gn, 64R); Functional Description - Siemens Siprotec 7UM62 Manual

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

2.27

Sensitive Earth Fault Protection (ANSI 51GN, 64R)

2.27.1 Functional Description

General
Application as
Rotor Earth Fault
Protection
Measuring
Procedure
7UM62 Manual
C53000-G1176-C149-3
The highly sensitive earth fault protection has the task to detect earth fault in systems
with isolated or high-impedance earthed star-point. The pick-up criterion is the
magnitude of the (residual) earth current. The magnitude of the residual current allows
earth fault detection, for example, on electrical machines which are directly connected
to the busbar of an isolated power system, when in case of a network earth fault the
machine supplies only a negligible earth fault current across the measurement
location, which must be situated between the machine terminals and the network,
whereas in case of a machine earth fault the higher earth fault current produced by the
total network is available. The measured current may be derived from toroidal CTs or
CTs in Holmgreen connection.
In the 7UM62, the sensitive earth fault detection feature can be allocated to either
input I
or I
. This choice is made during configuration (see Section 2.2).
EE1
EE2
This protection is not suited for detection of high earth currents which may arise in
case of earthed system starpoints (higher than approx. 1 A at the relay terminals for
highly sensitive earth current protection). If this protection feature nevertheless shall
be used as short-circuit to earth protection, an additional, external current transformer
is required as intermediate transformer.
Note: The sensitive earth current protection as well as for the directional or non–
directional stator earth fault protection of busbar-connected machines may use the
same current measuring input (I
identical input currents if address 0150 S/E/F PROT. is set to directional or
non-dir. U0&I0.
Alternatively, this protection can be used as rotor earth fault protection when a system
frequency bias voltage is applied to the rotor circuit (refer to Figure 2-88). In this case,
the measured current is determined by the magnitude of the bias voltage U
capacitance of the coupling capacitors of the rotor circuit.
A measured value supervision is provided for the application as rotor earth fault
protection: The measurement circuit is assumed to be closed as long as a small earth
current IEE< is flowing which is determined by the rotor-earth capacitance. If not, an
alarm is issued after a short delay time of 2 s.
Initially, the residual current is numerically filtered so that only the fundamental wave
of the current is used for the measurement. This makes the measurement insensitive
to transient conditions at the inception of a short-circuit and to harmonics content in
the current.
The protection consists of two stages. A pickup is detected as soon as the first
parameterized threshold value IEE> is exceeded. The trip command is transmitted
subsequent to the T IEE> delay time. A pickup is detected as soon as the second
parameterized threshold value IEE>> is exceeded. The trip command is transmitted
subsequent to the T IEE>> delay time.
Both stages can be blocked via a binary input.
Sensitive Earth Fault Protection (ANSI 51GN, 64R)
). That means that both protection functions use
EE2
and the
V
185