Settings Of The Vector Jump Detection - Siemens Siprotec 7UM62 Manual

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Pickup Values
Time Delays

2.25.2.1 Settings of the Vector Jump Detection

Addr.
Setting Title
4601
VECTOR JUMP
4602
DELTA PHI
4603
T DELTA PHI
4604
T RESET
4605A
U MIN
4606A
U MAX
4607A
T BLOCK
7UM62 Manual
C53000-G1176-C149-3
The value to be set for the vector jump (address 4602 DELTA PHI) depends on the
feeding and load conditions. Abrupt load changes in the active power cause a jump of
the voltage vector. The value to be set must be specifically determined for the power
system considered. This can be done on the basis of the equivalent circuit diagram in
Figure 2-80, or by means of a network calculation software.
If the setting is too sensitive, the protection function is likely to perform a network de-
coupling every time loads are connected or disconnected. Therefore, the default set-
ting is 10°.
The permissible voltage operating range can be set in the addresses 4605A for U MIN
and 4606A for U MAX. The limit values of the setting range are to some extent a matter
of the utility's philosophy. The value for U MIN should be less than the permissible
level of short voltage dips for which network decoupling is required. The default setting
is 80 % of the rated voltage. U MAX should be the maximum permissible voltage. This
will be in most cases 130 % of the rated voltage.
The time delay T DELTA PHI (address 4603) should be left at zero, except if you
wish to transmit the trip indication with a delay to a logic (CFC), or to leave enough
time for an external blocking to take effect.
After expiry of the timer T RESET (address 4604), the protection function is automat-
ically reset. The reset time depends on the decoupling philosophy. It must have ex-
pired before the circuit breaker is reclosed. Where the automatic reset function is not
used, the timer is set to ∞. The reset signal must come in that case from the binary
input (circuit breaker auxiliary contact).
The timer T BLOCK with reset delay (address 4607A) helps to avoid overfunctioning
when voltages are connected or disconnected. Normally, the default setting need not
be changed. If changes are necessary, they can be performed with the DIGSI commu-
nication software (advanced parameters). It must be kept in mind that T BLOCK should
always be set to more than the measuring window for vector jump measurement (2
cycles).
Setting Options
OFF
ON
Block relay for trip com-
mands
2..30 °
0.00..60.00 sec; ∞
0.10..60.00 sec; ∞
10.0..125.0 V
10.0..170.0 V
0.00..60.00 sec; ∞
Default Setting
OFF
Jump of Voltage Vector
10 °
Jump of Phasor DELTA PHI
0.00 sec
T DELTA PHI Time Delay
5.00 sec
Reset Time after Trip
80.0 V
Minimal Operation Voltage U
MIN
130.0 V
Maximal Operation Voltage U
MAX
0.10 sec
Time Delay of Blocking
Jump of Voltage Vector
Comments