Siemens Siprotec 7UM62 Manual page 154

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Functions
Power Swing
Polygon
138
The current I is independent of the location of the measurement:
U
G
I(m)
--------------------- -
=
I
=
Z
tot
The voltage U at the location of measurement m is:
(
U(m)
U
m Z
=
G
Thus results with:
j δ
G
U
U
e
=
G
G
1
Z(m)
------------------------------------ - m
=
U
æ
N
1
------- - e
è
U
G
where δ is the displacement angle between the generator voltage and the network
equivalent voltage. Under normal conditions, this angle depends on the load situation
and is nearly constant. It fluctuates during power swings and can vary, in case of an
out-of-step condition, between 0° and 360°. Figure 2-66 shows the trajectory of the
impedance vector at the measurement location m according to the above formula. The
origin of the coordinate system corresponds to the measurement location (voltage
transformer set). When the ratio of the voltage magnitudes U
the load angle δ varies, then circles result as a locus diagram. The centre and the
radius of the circle are determined by the ratio U
on a line which is determined by Z
measured impedance are at load angles δ = 0° and δ = 180°. If the measurement
location is the electrical centre, the measured voltage, and thus the measured
impedance, becomes zero when the load angle becomes δ = 180°.
The measurement characteristic is a rectangle with adjustable widths and inclination
angle ϕ
. This ensures optimum matching to the conditions in the power station.
P
U
N
)
I
tot
U
U
e
=
N
N
Z
tot
j δ
ö
ø
. Minimum and maximum of the magnitude of the
tot
j δ
δ
δ
N
=
G
/U
is kept constant and
N
G
/U
. The centre points are situated
N
G
C53000-G1176-C149-3
δ
N
7UM62 Manual