Siemens Siprotec 7UM62 Manual page 548

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

A Appendix
Addr.
Setting Title
4006A U< DOUT RATIO
4101
OVERVOLTAGE
4102
U>
4103
T U>
4104
U>>
4105
T U>>
4106A U> DOUT RATIO
4107A VALUES U>
4201
O/U FREQUENCY
4202
f1 PICKUP
4203
f1 PICKUP
4204
T f1
4205
f2 PICKUP
4206
f2 PICKUP
4207
T f2
4208
f3 PICKUP
4209
f3 PICKUP
4210
T f3
4211
f4 PICKUP
4212
f4 PICKUP
532
Function
Setting Options
Undervoltage
1.01..1.20
Protection
Overvoltage
OFF
Protection
ON
Block relay for trip
commands
Overvoltage
30.0..170.0 V
Protection
0.00..60.00 sec; ∞
Overvoltage
Protection
Overvoltage
30.0..170.0 V
Protection
0.00..60.00 sec; ∞
Overvoltage
Protection
Overvoltage
0.90..0.99
Protection
Overvoltage
Voltage protection
Protection
with U-Phase-Phase
Voltage protection
with U-Phase-earth
Frequency Pro-
OFF
tection
ON
Block relay for trip
commands
Frequency Pro-
40.00..65.00 Hz
tection
Frequency Pro-
40.00..65.00 Hz
tection
Frequency Pro-
0.00..600.00 sec
tection
Frequency Pro-
40.00..65.00 Hz
tection
Frequency Pro-
40.00..65.00 Hz
tection
Frequency Pro-
0.00..100.00 sec
tection
Frequency Pro-
40.00..65.00 Hz
tection
Frequency Pro-
40.00..65.00 Hz
tection
Frequency Pro-
0.00..100.00 sec
tection
Frequency Pro-
40.00..65.00 Hz
tection
Frequency Pro-
40.00..65.00 Hz
tection
Default Setting
1.05
U< Drop Out Ratio
OFF
Overvoltage Protection
115.0 V
U> Pickup
3.00 sec
T U> Time Delay
130.0 V
U>> Pickup
0.50 sec
T U>> Time Delay
0.95
U> Drop Out Ratio
Voltage protection
Measurement Values for
with U-Phase-Phase
U>
OFF
Over / Under Frequency
Protection
48.00 Hz
f1 Pickup
58.00 Hz
f1 Pickup
1.00 sec
T f1 Time Delay
47.00 Hz
f2 Pickup
57.00 Hz
f2 Pickup
6.00 sec
T f2 Time Delay
49.50 Hz
f3 Pickup
59.50 Hz
f3 Pickup
20.00 sec
T f3 Time Delay
52.00 Hz
f4 Pickup
62.00 Hz
f4 Pickup
Comments
7UM62 Manual
C53000-G1176-C149-3

Advertisement

Table of Contents
loading