Information For The Rotor Earth Fault Protection - Siemens Siprotec 7UM62 Manual

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Addr.
Setting Title
6006
X COUPLING
6007
R SERIES
6008
I RE<
6009
PHI I RE

2.30.2.2 Information for the Rotor Earth Fault Protection

F.No.
Alarm
05383 >BLOCK R/E/F
05391 R/E/F OFF
05392 R/E/F BLOCKED
05393 R/E/F AKTIVE
05394 R/E/F U< block
05397 R/E/F warning
05400 Failure R/E/F
05398 R/E/F picked up
05399 R/E/F TRIP
7UM62 Manual
C53000-G1176-C149-3
Setting Options
-100..800 Ohm
0..999 Ohm
1.0..50.0 mA; 0
-15.0..15.0 °
>BLOCK rotor earth fault prot. (R,fn)
Rotor earth fault prot. (R,fn) swit. OFF
Rotor earth fault prot. (R,fn) BLOCKED
Rotor earth fault prot. (R,fn) is ACTIVE
Rot. earth flt. prot. (R,fn) block by U<
Rot. earth flt.prot. (R,fn) Re< warning
Failure rotor earth fault prot. (R,fn)
Rot. earth flt.prot. (R,fn) Re<< pick.up
Rotor earth fault prot. (R,fn) Re<< TRIP
Rotor Earth Fault Protection R, fn (ANSI 64R)
Default Setting
398 Ohm
Coupling Reactance
50 Ohm
Series Resistance (e.g. Meas.
Brushes)
2.0 mA
Pickup Value of Failure Detec-
tion Ire<
0.0 °
Correction Angle for Ire
Comments
Comments
205

Advertisement

Table of Contents
loading