3 Installation and Commissioning
Changing the
Operating State
Test in the
Transmission
Direction
Exiting the
Procedure
348
Figure 3-17
Dialog Box: Generate indications
Following the first operation of one of the keys in the column Action a prompt for the
entry of password No. 6 (for hardware test menus) appears. After correct entry of the
password, individual messages can be initiated. To do this, click on the button Send
in the corresponding line. The corresponding message is initiated and can now be
retrieved as part of the operational alarms in the SIPROTEC
the central or master station of the plant.
Further tests remain possible while the dialog box is open.
For all information that has to be transmitted to the control system, open the drop-
down list in the column SETPOINT status and test the alternatives listed there:
G
Ensure that any switching operations that may result from these tests can be
executed without danger (see above under DANGER!).
G
With the function to be tested, click on send, and check that the corresponding
information is received at the central or master station, and, if required, the
expected response results.
To end the interface test, click on Close. The dialog box closes. The device becomes
unavailable for a brief start-up period immediately after this.
®