Addr.
Setting Title
3314
P/SPOL-TPOL
3315
dZ/dt
3316A BLOCKING OF
3317A T-ACTION P/S
3501
OUT-OF-STEP
3502
I1> RELEASE
3503
I2< RELEASE
3504
Za
3505
Zb
3506
Zc
3507
Zd - Zc
3508
PHI POLYGON
3509
REP. CHAR. 1
3510
REP. CHAR. 2
3511
T-HOLDING
3512
T-SIGNAL
4001
UNDERVOLTAGE
4002
U<
4003
T U<
4004
U<<
4005
T U<<
7UM62 Manual
C53000-G1176-C149-3
Function
Setting Options
Impedance Pro-
0.10..30.00 Ohm
tection
Impedance Pro-
1.0..600.0 Ohm/s
tection
Impedance Pro-
Zone Z1
tection
Zone Z1 and Z2
0.00..60.00 sec; ∞
Impedance Pro-
tection
Out-of-Step
OFF
Protection
ON
Block relay for trip
commands
Out-of-Step
20.0..400.0 %
Protection
Out-of-Step
5.0..100.0 %
Protection
Out-of-Step
0.20..130.00 Ohm
Protection
Out-of-Step
0.10..130.00 Ohm
Protection
Out-of-Step
0.10..130.00 Ohm
Protection
Out-of-Step
0.00..130.00 Ohm
Protection
60.0..90.0 °
Out-of-Step
Protection
Out-of-Step
1..4
Protection
Out-of-Step
1..8
Protection
Out-of-Step
0.20..60.00 sec
Protection
Out-of-Step
0.02..0.15 sec
Protection
Undervoltage
OFF
Protection
ON
Block relay for trip
commands
Undervoltage
10.0..125.0 V
Protection
0.00..60.00 sec; ∞
Undervoltage
Protection
Undervoltage
10.0..125.0 V
Protection
0.00..60.00 sec; ∞
Undervoltage
Protection
Default Setting
8.00 Ohm
Distance betw. Power
Swing - Trip-Pol.
300.0 Ohm/s
Rate of Change of dZ/dt
Zone Z1
Power Swing Blocking
locks out
3.00 sec
Power Swing Action Time
OFF
Out-of-Step Protection
120.0 %
Pickup Current for Measu-
ring Release I1>
20.0 %
Pickup Current for Measu-
ring Release I2<
4.50 Ohm
Resistance Za of the Poly-
gon (width)
12.00 Ohm
Reactance Zb of the Poly-
gon (reverse)
3.60 Ohm
Reactance Zc of Polygon
(forward char.1)
6.40 Ohm
Reactance Dif. Char.1 -
Char.2 (forward)
90.0 °
Angle of Inclination of the
Polygon
1
Number of Power Swing:
Characteristic 1
4
Number of Power Swing:
Characteristic 2
20.00 sec
Holding Time of Fault
Detection
0.05 sec
Min. Signal Time for Annun.
Char. 1/2
OFF
Undervoltage Protection
75.0 V
U< Pickup
3.00 sec
T U< Time Delay
65.0 V
U<< Pickup
0.50 sec
T U<< Time Delay
A.12 Settings