Siemens Siprotec 7UM62 Manual page 545

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Addr.
Setting Title
2110
I-REF>
2112
T I-REF>
2113A SLOPE
2114A BASE POINT
3001
UNDEREXCIT.
3002
1/xd CHAR. 1
3003
ANGLE 1
3004
T CHAR. 1
3005
1/xd CHAR. 2
3006
ANGLE 2
3007
T CHAR. 2
3008
1/xd CHAR. 3
3009
ANGLE 3
3010
T CHAR 3
3011
T SHRT Uex<
3012
EXCIT. VOLT.
3013
Uexcit. <
3014A Umin
3101
REVERSE
POWER
3102
P> REVERSE
3103
T-SV-OPEN
7UM62 Manual
C53000-G1176-C149-3
Function
Setting Options
Restricted Earth
0.05..2.00 I/InO
Fault Protection
0.00..60.00 sec; ∞
Restricted Earth
Fault Protection
Restricted Earth
0.00..0.95
Fault Protection
Restricted Earth
0.00..2.00 I/InO
Fault Protection
Underexcitation
OFF
Protection
ON
Block relay for trip
commands
Underexcitation
0.25..3.00
Protection
50..120 °
Underexcitation
Protection
0.00..60.00 sec; ∞
Underexcitation
Protection
Underexcitation
0.25..3.00
Protection
50..120 °
Underexcitation
Protection
0.00..60.00 sec; ∞
Underexcitation
Protection
Underexcitation
0.25..3.00
Protection
50..120 °
Underexcitation
Protection
0.00..60.00 sec; ∞
Underexcitation
Protection
0.00..60.00 sec; ∞
Underexcitation
Protection
Underexcitation
ON
Protection
OFF
Underexcitation
0.50..8.00 V
Protection
Underexcitation
10.0..125.0 V
Protection
Reverse Power
OFF
Protection
ON
Block relay for trip
commands
Reverse Power
-30.00..-0.50 %
Protection
0.00..60.00 sec; ∞
Reverse Power
Protection
Default Setting
0.10 I/InO
I-REF> Pickup
0.00 sec
T I-REF> Time Delay
0.25
Slope of Charac. I-REF> =
f(I0-Rest)
0.00 I/InO
Base Point for Slope of
Characteristic
OFF
Underexcitation Protection
0.41
Conductance Intersect
Characteristic 1
80 °
Inclination Angle of Charac-
teristic 1
10.00 sec
Characteristic 1 Time Delay
0.36
Conductance Intersect
Characteristic 2
90 °
Inclination Angle of Charac-
teristic 2
10.00 sec
Characteristic 2 Time Delay
1.10
Conductance Intersect
Characteristic 3
90 °
Inclination Angle of Charac-
teristic 3
0.30 sec
Characteristic 3 Time Delay
0.50 sec
T-Short Time Delay (Char.
& Uexc<)
OFF
State of Excitation Volt.
Supervision
2.00 V
Excitation Voltage Superv.
Pickup
25.0 V
Undervoltage blocking Pik-
kup
OFF
Reverse Power Protection
-1.93 %
P> Reverse Pickup
10.00 sec
Time Delay Long (without
Stop Valve)
A.12 Settings