Settings For The Tripping Logic; Fault Display On The Leds/Lcd; Principle Of Function; Settings - Siemens Siprotec 7UM62 Manual

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Addr.
Parameter
0280
TMin TRIP CMD.

2.44.3 Fault Display on the LEDs/LCD

2.44.3.1 Principle of Function

2.44.3.2 Settings

Addr.
Parameter
7110
FltDisp.LED/LCD
7UM62 Manual
C53000-G1176-C149-3
that can initiate trip signals, as well as for trip signals that are initiated using the device
function controller.
Setting
0.01 .. 32.00 s
The storage of messages masked to local LEDs, and the maintenance of spontaneous
messages, can be made dependent on whether the device has issued a trip signal. In
this situation, these messages are not issued, if one or more protective functions have
only picked up on a fault, but a trip signal has not been issued yet by the 7UM62
because the fault was cleared by another device (for instance outside of the own
protection range). These messages are then limited to faults in the own protection
range. Figure 2-132 illustrates the creation of the reset command for stored
messages. By the moment of the device dropout, the stationary conditions (fault
indication with excitation/with trip signal; tripping/no tripping) decide whether the new
fault remains stored or is reset.
7110
FltDisp.LED/LCD
Targets on every pickup
"1"
Targets on TRIP only
Relay TRIP
Trip Signal drop out
Figure 2-132 Creation of the reset command for the memory of the LED and LCD messages
Pickup of a new protective function generally turns off any previously set light displays,
so that only the latest fault is displayed at any time. It can be selected whether the
stored LED displays and the spontaneous messages on the display appear upon
renewed pickup, or only after a renewed trip signal is issued. In order to enter the
desired type of display, select in the SETTINGS menu the sub-menu Device. Address
7110 FltDisp.LED/LCD offers the two alternatives Display Targets on
every Pickup and Display Target on TRIP only.
Setting
Display Targets on every
Pickup
Display Targets on TRIP only
Default Settings
0.15 s
Minimum duration of the trip
command
&
Reset LED and LCD messages
Default Settings
Display Targets on
Fault display on the LEDs/LCD
every Pickup
Protection Function Logic
Comment
Comment
283