Destination: Indication Buffer, System Interface - Siemens Siprotec 7UM62 Manual

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

A Appendix
A.8.2

Destination: Indication Buffer, System Interface

Configuring an In-
dication Buffer as a
Destination
Configuring the
SCADA Interface
as a Destination
510
Two indication buffers are available for selection: Operation (Event Log) Buffer (E) and
Trip Log (T). The indications from protective functions are firmly assigned to these in-
dication buffers. For the others, Table A-6 provides an overview of which indication
type may be configured to which buffer.
Table A-6
Overview of Indication Buffers
Information type ↓ \Message buffer →
Single Point Indications (SP)
Double Point Indications (DP)
Output Indications (OUT)
Internal Single Point Indications (IntSP)
Internal Double Point Indications (DP)
Transformer Tap Change Indications (TxTap)
Depending on the SCADA interfaces connected to the relay, the types of information
displayed in Table A-7 may be configured. By placing an X in the matrix cell, the infor-
mation is transferred to connected systems via the SCADA interface.
.
Overview of SCADA Interfaces
Table A-7
SCADA Interface →
Information Type ↓
Single Point Indication (SP)
Double Point Indication (DP)
Output Indication (OUT)
Internal Single Point Indicator (IntSP)
Internal Double Point Indicator (IntDP)
Transformer Tap Change Indicator (TxTap)
Command with/without Feedback (C_**)
Protective Measurement Value
Protective Measurement Value with Time
(MVT)
Protective Measurement Value, User
Defined (MVU)
Pulsed Metered Value (PMV)
Metered Value from Measurement Value
(MVMV)
E
T
X
X
X
X
X
X
X
X
X
IEC
Profi-
Modbus DNP3.0
bus DP
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
C53000-G1176-C149-3
X
X
X
X
X
X
X
X
7UM62 Manual