Siemens Siprotec 7UM62 Manual page 551

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Addr.
Setting Title
4514
df4/dt >/<
4515
STAGE df4/dt
4516
T df4/dt
4517
df4/dt & f4
4518
U MIN
4519A df1/2 HYSTERES.
4520A df1/2 M-WINDOW
4521A df3/4 HYSTERES.
4522A df3/4 M-WINDOW
4601
VECTOR JUMP
4602
DELTA PHI
4603
T DELTA PHI
4604
T RESET
4605A U MIN
4606A U MAX
4607A T BLOCK
5001
S/E/F PROT.
7UM62 Manual
C53000-G1176-C149-3
Function
Setting Options
Rate-of-fre-
-df/dt< negative rate
quency-change
of freq. change
protection
+df/dt> positive rate
of freq. change
0.1..10.0 Hz/s; ∞
Rate-of-fre-
quency-change
protection
0.00..60.00 sec; ∞
Rate-of-fre-
quency-change
protection
Rate-of-fre-
OFF
quency-change
ON
protection
Rate-of-fre-
10.0..125.0 V; 0
quency-change
protection
Rate-of-fre-
0.02..0.99 Hz/s
quency-change
protection
Rate-of-fre-
1..25 Cycle
quency-change
protection
Rate-of-fre-
0.02..0.99 Hz/s
quency-change
protection
Rate-of-fre-
1..25 Cycle
quency-change
protection
Jump of Voltage
OFF
Vector
ON
Block relay for trip
commands
2..30 °
Jump of Voltage
Vector
0.00..60.00 sec; ∞
Jump of Voltage
Vector
0.10..60.00 sec; ∞
Jump of Voltage
Vector
Jump of Voltage
10.0..125.0 V
Vector
Jump of Voltage
10.0..170.0 V
Vector
0.00..60.00 sec; ∞
Jump of Voltage
Vector
Stator Earth
OFF
Fault Protection
ON
Block relay for trip
commands
Default Setting
-df/dt< negative rate
Mode of Threshold (df4/dt
of freq. change
>/<)
4.0 Hz/s
Pickup Value of df4/dt
Stage
0.00 sec
Time Delay of df4/dt Stage
OFF
AND logic with pickup of
stage f4
65.0 V
Minimum Operating
Voltage Umin
0.10 Hz/s
Reset Hysteresis for df1/dt
& df2/dt
5 Cycle
Measuring Window for df1/
dt & df2/dt
0.40 Hz/s
Reset Hysteresis for df3/dt
& df4/dt
5 Cycle
Measuring Window for df3/
dt & df4/dt
OFF
Jump of Voltage Vector
10 °
Jump of Phasor DELTA
PHI
0.00 sec
T DELTA PHI Time Delay
5.00 sec
Reset Time after Trip
80.0 V
Minimal Operation Voltage
U MIN
130.0 V
Maximal Operation Voltage
U MAX
0.10 sec
Time Delay of Blocking
OFF
Stator Earth Fault Protec-
tion
A.12 Settings
Comments
535