Siemens Siprotec 7UM62 Manual page 543

Multifunction generator, motor and transformer protection relay
Hide thumbs Also See for Siprotec 7UM62:
Table of Contents

Advertisement

Addr.
Setting Title
1612A Kτ-FACTOR
1615A I MAX THERM.
1616A T EMERGENCY
1701
UNBALANCE
LOAD
1702
I2>
1703
T WARN
1704
FACTOR K
1705
T COOL DOWN
1706
I2>>
1707
T I2>>
1801
O/C STARTUP
1802
STARTUP I>
1803
STARTUP T I>
2001
DIFF. PROT.
2005
INC.CHAR.START
2006
INRUSH 2.HARM.
2007
RESTR. n.HARM.
7UM62 Manual
C53000-G1176-C149-3
Function
Setting Options
Thermal Over-
1.0..10.0
load Protection
Thermal Over-
0.50..8.00 A
load Protection
Thermal Over-
10..15000 sec
load Protection
Unbalance
OFF
Load (Negative
ON
Sequence)
Block relay for trip
commands
Unbalance
3.0..30.0 %
Load (Negative
Sequence)
0.00..60.00 sec; ∞
Unbalance
Load (Negative
Sequence)
2.0..100.0 sec; ∞
Unbalance
Load (Negative
Sequence)
Unbalance
0..50000 sec
Load (Negative
Sequence)
Unbalance
10..100 %
Load (Negative
Sequence)
0.00..60.00 sec; ∞
Unbalance
Load (Negative
Sequence)
Startup O/C
OFF
protection
ON
Block relay for trip
commands
Startup O/C
0.10..20.00 A
protection
0.00..60.00 sec; ∞
Startup O/C
protection
Differential Pro-
OFF
tection
ON
Block relay for trip
commands
Differential Pro-
OFF
tection
ON
Differential Pro-
OFF
tection
ON
Differential Pro-
OFF
tection
3. Harmonic
5. Harmonic
Default Setting
1.0
Kt-Factor when Motor
Stops
3.30 A
Maximum Current for Ther-
mal Replica
100 sec
Emergency Time
OFF
Unbalance Load Protection
10.6 %
Continously Permissible
Current I2
20.00 sec
Warning Stage Time Delay
18.7 sec
Negativ Sequence Factor K
1650 sec
Time for Cooling Down
60 %
I2>> Pickup
3.00 sec
T I2>> Time Delay
OFF
Startup O/C protection
1.30 A
I> Pickup
0.50 sec
T I> Time Delay
OFF
Differential Protection
OFF
Increase of Trip Char.
During Start
ON
Inrush with 2. Harmonic
Restraint
OFF
n-th Harmonic Restraint
A.12 Settings
Comments
527